Low-temperature unit (air-cooled) ANL 178 TTK 100/35WL-2-E

Low-temperature unit (air-cooled) ANL 178 TTK 100/35WL-2-E

Cooling capacity

-

Dimensions

6100 x 2450 x 2600 mm

Weight

8500 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph
Max. operating current365 A
Minimum cable cross-section for 25 m feed5x 185 mm²
Refrigeration circuit
RefrigerantR507A
Number of refrigeration circuits2
Consumer circuit
Internal pump3,5 bar
Volume flow30
Dimensions and weight
Length6100 mm
Width2450 mm
Height2600 mm
Weight8500 kg
Connections
Consumer2x Flansch DN 100
Operating environment
Max. 35 °C Außentemperatur
Coolant
Tyfoxit F 50, Calciumchlorid 30 %,
Wasser / Glykol
Special equipment
Fernwartung: UMTS-Router
Leistungsmessung: Kälteleistung

Cooling capacity [kW]

Supply temperature
Outdoor
temp.
-10 °C -15 °C -20 °C -25 °C -30 °C -35 °C -40 °C
35 °C - - - 150 122 99 78
25 °C - - - 170 140 113 90