Low-temperature unit (water-cooled) ANL 186 TTK 250/30W-1

Low-temperature unit (water-cooled) ANL 186 TTK 250/30W-1

Cooling capacity

227 kW

Dimensions

2991 x 2438 x 2591 mm

Weight

4000 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph+N
Max. current draw570 A
Minimum cable cross-section for 25 m feed2x 5x 185 mm² (Doppelt auflegen)
Refrigeration circuit
RefrigerantR449A
Number of refrigeration circuits1
Number of compressors1
Dimensions and weight
Length2991 mm
Width2438 mm
Height2591 mm
Weight4000 kg
Connections
ConsumerFlansch DN 100
Operating environment
Max. 35 °C Außentemperatur
Coolant
Wasser / Glykol
Special equipment
Fernwartung: UMTS-Router

Table 1: Water-cooled at +38 °C inlet (e.g. glycol) tc = 48 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 - - - - - -
-35 - - - -
-30 - - - - - -
-25 -30 100 289 241 394 433
-20 -25 100 361 250 408 531

Table 2: Water-cooled at +27 °C inlet (e.g. cooling tower) tc = 37 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 - - - - - -
-35 -40 100 201 176 297 311
-30 -35 100 257 183 307 391
-25 -30 100 322 191 318 482
-20 -25 100 398 199 330 585

Table 3: Water-cooled at +8 °C inlet (e.g. chiller) tc = 20 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 - - - - - -
-35* -40* 100* 227* 123* 225* 346*
-30 -35 100 287 130 233 421
-25 -30 100 357 135 240 498
-20 -25 100 437 140 246 585

The cooling capacity stated above is the net capacity at the evaporator. The heat input into the hydraulic system caused by external pumps and insulation losses must be taken into account.

* Rated operating point