| Electrical data | |
|---|---|
| Supply voltage | 400 V / 50 Hz / 3 Ph+N |
| Max. current draw | 570 A |
| Minimum cable cross-section for 25 m feed | 2x 5x 185 mm² (Doppelt auflegen) |
| Refrigeration circuit | |
|---|---|
| Refrigerant | R449A |
| Number of refrigeration circuits | 1 |
| Number of compressors | 1 |
| Dimensions and weight | |
|---|---|
| Length | 2991 mm |
| Width | 2438 mm |
| Height | 2591 mm |
| Weight | 4000 kg |
| Connections | |
|---|---|
| Consumer | Flansch DN 100 |
| Operating environment |
|---|
| Max. 35 °C Außentemperatur |
| Coolant |
|---|
| Wasser / Glykol |
| Special equipment |
|---|
| Fernwartung: UMTS-Router |
| Brine temperature [°C] |
Evaporation [°C] |
Capacity control [%] |
Cooling capacity [kW] |
Electrical power [kW] |
Current draw [A] |
Heat output [kW] |
|---|---|---|---|---|---|---|
| -40 | - | - | - | - | - | - |
| -35 | - | - | - | - | ||
| -30 | - | - | - | - | - | - |
| -25 | -30 | 100 | 289 | 241 | 394 | 433 |
| -20 | -25 | 100 | 361 | 250 | 408 | 531 |
| Brine temperature [°C] |
Evaporation [°C] |
Capacity control [%] |
Cooling capacity [kW] |
Electrical power [kW] |
Current draw [A] |
Heat output [kW] |
|---|---|---|---|---|---|---|
| -40 | - | - | - | - | - | - |
| -35 | -40 | 100 | 201 | 176 | 297 | 311 |
| -30 | -35 | 100 | 257 | 183 | 307 | 391 |
| -25 | -30 | 100 | 322 | 191 | 318 | 482 |
| -20 | -25 | 100 | 398 | 199 | 330 | 585 |
| Brine temperature [°C] |
Evaporation [°C] |
Capacity control [%] |
Cooling capacity [kW] |
Electrical power [kW] |
Current draw [A] |
Heat output [kW] |
|---|---|---|---|---|---|---|
| -40 | - | - | - | - | - | - |
| -35* | -40* | 100* | 227* | 123* | 225* | 346* |
| -30 | -35 | 100 | 287 | 130 | 233 | 421 |
| -25 | -30 | 100 | 357 | 135 | 240 | 498 |
| -20 | -25 | 100 | 437 | 140 | 246 | 585 |
The cooling capacity stated above is the net capacity at the evaporator. The heat input into the hydraulic system caused by external pumps and insulation losses must be taken into account.
* Rated operating point