Low-temperature unit (water-cooled) ANL 178 TTK 100/35WL-2-E

Low-temperature unit (water-cooled) ANL 178 TTK 100/35WL-2-E

Cooling capacity

127.8 kW

Dimensions

6100 x 2450 x 2600 mm

Weight

8500 kg

Electrical data
Supply voltage400V / 50Hz / 3Ph
Max. current draw365 A
Minimum cable cross-section for 25 m feed5x 185 mm²
Refrigeration circuit
RefrigerantR507A
Number of refrigeration circuits2
Consumer circuit
Pump head3,5 bar
Volume flow30
Dimensions and weight
Length6100 mm
Width2450 mm
Height2600 mm
Weight8500 kg
Connections
Consumer2x Flansch DN 100
Operating environment
Max. 35 °C Außentemperatur
Coolant
Tyfoxit F 50
Calciumchlorid 30 %
Wasser / Glykol
Special equipment
Fernwartung: UMTS-Router
Leistungsmessung: Kälteleistung

Table 1: Water-cooled at +38 °C inlet (e.g. glycol) tc = 48 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 -45 100 78.6 126.8 201.2 147.4
-35 -40 100 99.6 131 207.6 181.6
-30 -35 100 123.6 136 215.2 219.8
-25 -30 100 150.6 141.6 223.4 261.8
-20 -25 100 181.6 147.4 232.2 308.6

Table 2: Water-cooled at +27 °C inlet (e.g. cooling tower) tc = 37 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 -45 100 91 98.8 159.6 166.6
-35 -40 100 114.2 103.6 166.6 204.6
-30 -35 100 141 108.4 174 247
-25 -30 100 172 113.4 181.4 289.8
-20 -25 100 207.2 118.4 189 331.2

Table 3: Water-cooled at +8 °C inlet (e.g. chiller) tc = 20 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 -45 100 101.2 71.2 119.2 174.4
-35* -40* 100* 127.8* 75.2* 125* 205.8*
-30 -35 100 158.6 79.2 130.8 241.4
-25 -30 100 194 83.4 136.6 281.8
-20 -25 100 234.6 87.6 143 327.8

The cooling capacity stated above is the net capacity at the evaporator. The heat input into the hydraulic system caused by external pumps and insulation losses must be taken into account.

* Rated operating point

Noch Fragen? Kontaktieren Sie uns!