Low-temperature unit (water-cooled) ANL 147 TTK 140/35WL-2

Low-temperature unit (water-cooled) ANL 147 TTK 140/35WL-2

Cooling capacity

178.4 kW

Dimensions

6100 x 2450 x 2600 mm

Weight

8500 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph
Max. current draw375 A
Minimum cable cross-section for 25 m feed5x 185 mm²
Refrigeration circuit
RefrigerantR449A
Number of refrigeration circuits2
Consumer circuit
Pump head3,5 bar
Volume flow30
Dimensions and weight
Length6100 mm
Width2450 mm
Height2600 mm
Weight8500 kg
Connections
Consumer2x Flansch DN 100
Operating environment
Max. 35 °C Außentemperatur
Coolant
Tyfoxit F 50
Calciumchlorid 30 %
Wasser / Glykol
Special equipment
Fernwartung: UMTS-Router
Leistungsmessung: Kälteleistung

Table 1: Water-cooled at +38 °C inlet (e.g. glycol) tc = 48 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 - - - - - -
-35 -40 100 140.4 175.6 296.2 218
-30 -35 100 179.4 184.6 309.4 273
-25 -30 100 224.8 193 321.8 335.8
-20 -25 100 277.4 201.2 334.2 408

Table 2: Water-cooled at +27 °C inlet (e.g. cooling tower) tc = 37 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 -45 100 131 133.2 234.6 206.6
-35 -40 100 165.2 138.4 242.2 256
-30 -35 100 205.8 145 251.2 313
-25 -30 100 253.2 152.4 262 378.6
-20 -25 100 308.4 161 274.4 454

Table 3: Water-cooled at +8 °C inlet (e.g. chiller) tc = 20 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 -45 100 142.6 85.4 172 220.8
-35* -40* 100* 178.4* 92.4* 180.6* 271.8*
-30 -35 100 221 102 190.2 324.4
-25 -30 100 270.8 108.8 201.4 383.8
-20 -25 100 328.6 118.2 214 452

The cooling capacity stated above is the net capacity at the evaporator. The heat input into the hydraulic system caused by external pumps and insulation losses must be taken into account.

* Rated operating point

Noch Fragen? Kontaktieren Sie uns!