Low-temperature unit (water-cooled) ANL 144 TTK 90/35WL-2-E

Low-temperature unit (water-cooled) ANL 144 TTK 90/35WL-2-E

Cooling capacity

101 kW

Dimensions

6100 x 2450 x 2600 mm

Weight

7900 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph
Max. current draw317 A
Power at rated load129.9 kW
Minimum cable cross-section for 25 m feed5x 120 mm²
Refrigeration circuit
RefrigerantR449A
Number of refrigeration circuits2
Consumer circuit
Pump head3,5 bar
Volume flow30
Dimensions and weight
Length6100 mm
Width2450 mm
Height2600 mm
Weight7900 kg
Connections
Consumer2x Flansch DN 100
Operating environment
Max. 35 °C Außentemperatur
Coolant
Tyfoxit F 50
Calciumchlorid 30 %
Wasser / Glykol
Special equipment
Fernwartung: UMTS-Router
Leistungsmessung: Kälteleistung

Table 1: Water-cooled at +38 °C inlet (e.g. glycol) tc = 48 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 - - - - - -
-35 -40 100 86 113.6 181.6 133.4
-30 -35 100 109.6 119 189.8 167
-25 -30 100 137.2 124.2 197.6 205
-20 -25 100 177.2 129.2 204.8 248.2

Table 2: Water-cooled at +27 °C inlet (e.g. cooling tower) tc = 37 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 -45 100 77 82.6 135.6 121.4
-35 -40 100 98 87 142 151.8
-30 -35 100 122.8 91.6 148.6 186.8
-25 -30 100 151.6 96 155.4 226.8
-20 -25 100 185.2 100.8 162.4 272.4

Table 3: Water-cooled at +8 °C inlet (e.g. chiller) tc = 20 °C

Brine
temperature [°C]
Evaporation
[°C]
Capacity
control [%]
Cooling
capacity [kW]
Electrical
power [kW]
Current
draw [A]
Heat
output [kW]
-40 -45 100 79.2 53.4 95.4 122.6
-35* -40* 100* 101* 58.4* 101.8* 153.8*
-30 -35 100 126.8 62.8 107.8 190.2
-25 -30 100 157 67.2 113.8 226.8
-20 -25 100 192 71.8 120 267.2

The cooling capacity stated above is the net capacity at the evaporator. The heat input into the hydraulic system caused by external pumps and insulation losses must be taken into account.

* Rated operating point

Noch Fragen? Kontaktieren Sie uns!