Chiller ANL 170 WRK 132L-1-PT

Chiller ANL 170 WRK 132L-1-PT

Cooling capacity

109 - 211 kW

Dimensions

4320 x 1680 x 2200 mm

Weight

2050 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph
Max. current draw112.2 A
Power at rated load60.5 kW
Minimum cable cross-section for 25 m feed125 A CEE 5x35 mm²
Refrigeration circuit
RefrigerantR407C
Number of refrigeration circuits1
Number of compressors2
Consumer circuit
Internal pump3,06 - 1,47 bar
Volume flow36 - 84
Buffer tank500 l
Dimensions and weight
Length4320 mm
Width1680 mm
Height2200 mm
Weight2050 kg
Connections
Consumer3" Kamlok
Drain1/2" Geka
Operating environment
min. -15 °C bis max. 40 °C
Coolant
Wasser, Wasser / Glykol

Cooling capacity [kW]

Supply temperature
Outdoor
temp.
20 °C 15 °C 10 °C 5 °C 0 °C -5 °C -10 °C
35 °C 190 159 132 109 - - -
25 °C 211 177 147 122 - - -

Noch Fragen? Kontaktieren Sie uns!