Chiller ANL 185 WRK 441L-2-2P3T

Chiller ANL 185 WRK 441L-2-2P3T

Cooling capacity

301 - 593 kW

Dimensions

4455 x 2191 x 2423 mm

Weight

4154 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph
Max. current draw335 A
Power at rated load158 kW
Minimum cable cross-section for 25 m feed4x 185 mm²
Refrigeration circuit
RefrigerantR410A
Number of refrigeration circuits2
Number of compressors3
Consumer circuit
Internal pump3,0 - 2,5 bar
Volume flow30 - 90
Buffer tank800 l
Dimensions and weight
Length4455 mm
Width2191 mm
Height2423 mm
Weight4154 kg
Connections
ConsumerDN 125 Victaulic
Filling connection1/2"
Sound pressure level
at 10 m 60 dB(A)
Operating environment
min. -20 °C bis max. 47 °C
Coolant
Wasser, Wasser / Glykol

Cooling capacity [kW]

Supply temperature
Outdoor
temp.
20 °C 15 °C 10 °C 5 °C 0 °C -5 °C -10 °C
35 °C 521 500 437 354 301 - -
25 °C 593 566 497 403 344 - -

Noch Fragen? Kontaktieren Sie uns!