Chiller ANL 129 WRK 186L-2-PT

Chiller ANL 129 WRK 186L-2-PT

Cooling capacity

100 - 264 kW

Dimensions

5560 x 1310 x 2300 mm

Weight

2893 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph
Max. current draw149 A
Power at rated load66.3 kW
Minimum cable cross-section for 25 m feed4x 70 mm²
Refrigeration circuit
RefrigerantR410A
Number of refrigeration circuits2
Number of compressors2
Consumer circuit
Internal pump3,3 - 2,2 bar
Volume flow18,8 - 56
Buffer tank950 l
Dimensions and weight
Length5560 mm
Width1310 mm
Height2300 mm
Weight2893 kg
Connections
Consumer4" Kamlok
Filling connection1/2"
Sound pressure level
at 10 m 63.7 dB(A)
Operating environment
min. -5 °C bis max. -46 °C
Coolant
Wasser, Wasser / Glykol

Cooling capacity [kW]

Supply temperature
Outdoor
temp.
20 °C 15 °C 10 °C 5 °C 0 °C -5 °C -10 °C
35 °C 233 204 186 165 140 121 100
25 °C 264 232 211 189 160 139 116

Noch Fragen? Kontaktieren Sie uns!