Chiller ANL 110 WRK 111L-2-E-PT

Chiller ANL 110 WRK 111L-2-E-PT

Cooling capacity

54,8 - 141 kW

Dimensions

3300 x 1300 x 2400 mm

Weight

1831 kg

Electrical data
Supply voltage400 V / 50 Hz / 3 Ph
Electrical connection125 A CEE Stecker
Current at rated load58.1 A
Max. current draw93 A
Power at rated load40.2 kW
Minimum cable cross-section for 25 m feed125 A CEE 5x35 mm²
Refrigeration circuit
RefrigerantR410A
Number of refrigeration circuits2
Number of compressors2
Consumer circuit
Internal pump1,5 - 3,8 bar
Volume flow8,1 - 48
Buffer tank500 l
Dimensions and weight
Length3300 mm
Width1300 mm
Height2400 mm
Weight1831 kg
Connections
Consumer2" Kamlock
Filling connection1/2"
Sound pressure level
at 10 m 61.5 dB(A)
Operating environment
min. -20 °C bis max. 43 °C
Coolant
Wasser, Wasser / Glykol

Cooling capacity [kW]

Supply temperature
Outdoor
temp.
20 °C 15 °C 10 °C 5 °C 0 °C -5 °C -10 °C
35 °C - 123 109 95.1 78.4 66.2 54.8
25 °C - 141 125 109 90.8 77.4 65